The Effect of Upstream Buildings on Near-field Pollutant Dispersion in the Built Environment

Title:

The Effect of Upstream Buildings on Near-field Pollutant Dispersion in the Built Environment

Hajra, B., Stathopoulos, T. and Bahloul, A. (2011) The Effect of Upstream Buildings on Near-field Pollutant Dispersion in the Built Environment. Atmospheric Environment, 45 (28). pp. 4930-4940.

[thumbnail of The Effect of Upstream Buildings on Near-field Pollutant Dispersion in the Built Environment.pdf]
Preview
Text (application/pdf)
The Effect of Upstream Buildings on Near-field Pollutant Dispersion in the Built Environment.pdf
978kB

Official URL: http://dx.doi.org/10.1016/j.atmosenv.2011.06.008

Abstract

This paper examines the effects of near-field pollutant dispersion characteristics of upstream buildings in the built environment and compares them to the ASHRAE 2007 model. Wind tunnel simulations were performed for nine different building configurations for three exhaust momentum ratios (M) and three stack heights (hs). The effect of spacing (S) between the buildings and stack location from the upwind edge of the emitting building (X) were also investigated. Measurements of gas concentrations were performed on the roof and leeward wall of the emitting and upstream buildings. Data show that within the recirculation zone a change in along wind dimension of the upstream building has a negligible effect on the dilution of emissions from the downwind building. However, spacing between buildings and the height of the upstream building were found to be critical parameters in assessing plume dilution. The plume geometry is largely governed by the upwind dimensions of the upstream building. ASHRAE (2007) predicts lower dilution for all cases examined, leading to conservative or very conservative design. However, the ASHRAE 2007 cannot model the effect of upstream buildings, thus further investigation of its formulations is required. Guidelines for placement of intake and stack on the roof of the building to avoid problems of re-ingestion are discussed.

Divisions:Concordia University > Gina Cody School of Engineering and Computer Science > Building, Civil and Environmental Engineering
Item Type:Article
Refereed:Yes
Authors:Hajra, B. and Stathopoulos, T. and Bahloul, A.
Journal or Publication:Atmospheric Environment
Date:2011
Digital Object Identifier (DOI):10.1016/j.atmosenv.2011.06.008
ID Code:981684
Deposited By: Theodore Stathopoulos
Deposited On:20 Sep 2016 15:27
Last Modified:18 Jan 2018 17:53
All items in Spectrum are protected by copyright, with all rights reserved. The use of items is governed by Spectrum's terms of access.