Login | Register

Dynamic modeling, control and energy simulation of a solar-assisted hydronic space heating system in a multi-function building

Title:

Dynamic modeling, control and energy simulation of a solar-assisted hydronic space heating system in a multi-function building

Cai, Xiangyu (2019) Dynamic modeling, control and energy simulation of a solar-assisted hydronic space heating system in a multi-function building. Masters thesis, Concordia University.

[thumbnail of Cai_MASc_S2019.pdf]
Preview
Text (application/pdf)
Cai_MASc_S2019.pdf - Accepted Version
Available under License Spectrum Terms of Access.
4MB

Abstract

A dynamic model of a solar-assisted hydronic space heating system for a multi-function building has been developed. The system performance under different control strategies and the model-based energy simulations studies have been conducted. The system consists of several components including a boiler, heat exchangers, flat-plate solar collectors, a water storage tank, baseboard heaters and a radiant floor heating system. The model consists of nonlinear differential equations which were programmed and solved using the MATLAB software. Two control strategies have been explored to compare the system performance: (i) a conventional PI control and (ii) a gain-scheduling adaptive (GSA) PI control. The simulation results indicate that the system performance under GSA PI control is better than the conventional PI control with respect to disturbance rejection and stability. An optimization problem was formulated and solved to study the energy performance of the system. Preliminary simulation results with assumed outdoor temperature profiles showed that the optimized set-point operating strategy contributes 7% and 14.87% to boiler energy saving in mild and warm day conditions compared with constant set-point strategy. One week energy simulations under actual weather conditions based on typical meteorological year (TMY) data have been conducted to investigate the percent contribution of solar energy to space heating. The simulation results show that the solar system contributes less energy during cold winter conditions such as in the month of December. However, it can reduce 16.94% of boiler energy supplied to the radiant floor heating system in the month of March. Besides, the implementation of the optimal GSA PI control strategy can result in higher solar fractions of 5.71% and 30.36% as compared to the base case PI control under cold (December) and mild (March) weather conditions, respectively.

Divisions:Concordia University > Gina Cody School of Engineering and Computer Science > Building, Civil and Environmental Engineering
Item Type:Thesis (Masters)
Authors:Cai, Xiangyu
Institution:Concordia University
Degree Name:M.A. Sc.
Program:Building Engineering
Date:March 2019
Thesis Supervisor(s):Zaheeruddin, Mohammed
ID Code:985127
Deposited By: XIANGYU CAI
Deposited On:17 Jun 2019 18:43
Last Modified:17 Jun 2019 18:43
All items in Spectrum are protected by copyright, with all rights reserved. The use of items is governed by Spectrum's terms of access.

Repository Staff Only: item control page

Downloads per month over past year

Research related to the current document (at the CORE website)
- Research related to the current document (at the CORE website)
Back to top Back to top