Dou, Hongwen (2023) Fault detection and diagnosis (FDD) for multiple-dependent faults of chillers. PhD thesis, Concordia University.
Preview |
Text (application/pdf)
10MBDou_PhD_S2023.pdf - Accepted Version Available under License Spectrum Terms of Access. |
Abstract
As an indispensable system in modern buildings, the heating, ventilation, and air conditioning (HVAC) system usually takes a large proportion of building energy usage. However, faults of HVAC system in modern buildings are becoming a growing issue. These faults can aggravate equipment degradation or even damage equipment, and sequentially lead to the increase of maintenance cost and the significant energy waste. Therefore, it is paramount for the HVAC system to run as effectivity and fault free as possible; as a result, research and development into HVAC faults turns to an effective approach to improve building energy efficiency. This dissertation is a contribution to the research of fault detection and diagnosis with a new topic of chiller multiple dependent faults in a real building.
The forward fault detection model and the backward fault diagnosis model are developed to identify and isolate chiller system-level and component-level faults respectively, based on the measurement data from an institutional building. The second law of thermodynamics is applied to analyse the energy flow over an electric chiller, for the purpose of selecting target variables. Benchmarking grey-box models are developed to predict target variables, and sequentially to estimate the impacts of regressor variable faults on target variables. A fault symptom is detected when the residual of a target variable, the difference between the measured value and the predicted value, exceeds the corresponding threshold. Then, a backward rule-based approach is presented to identify if (i) the fault symptom is correct (i.e., a variable has abnormal values), or (ii) the fault symptom is incorrect (i.e., the symptom of target variable is caused by impacts generated by other faulty variables due to the dependency between variables), or (iii) both target and regressor variables are abnormal. The proposed model for chiller multiple-dependent faults is validated by a case study with a cooling plant serving an institutional building, where some faults are artificially inserted into the measurement data file. This dissertation also explored the effectiveness of transfer learning method in the application of improving deep learning model performance.
Divisions: | Concordia University > Gina Cody School of Engineering and Computer Science > Building, Civil and Environmental Engineering |
---|---|
Item Type: | Thesis (PhD) |
Authors: | Dou, Hongwen |
Institution: | Concordia University |
Degree Name: | Ph. D. |
Program: | Building Engineering |
Date: | 30 March 2023 |
Thesis Supervisor(s): | Radu, Zmeureanu |
ID Code: | 992031 |
Deposited By: | Hongwen Dou |
Deposited On: | 21 Jun 2023 14:27 |
Last Modified: | 21 Jun 2023 14:27 |